Product

L type condensing unit

L type condensing unit

■Fully enclosed air-cooled unit

Choose international brand refrigeration compressors, with good quality, high reliability, low noise and high efficiency. Using aluminum tube condenser with high heat exchange efficiency and long service life

Product Details

1. Product features:

Choose international brand refrigeration compressors, with good quality, high reliability, low noise and high efficiency. The use of aluminum tube condensers with high heat exchange efficiency.

long life.

 

2. Model description:

Note: The
cooling capacity in the table is the ambient temperature of 32℃, and the
configuration can be added according to requirements

 


Scroll series of medium and high temperature air-cooled condensing unit

Unit Type

XMF2MC

XMF3MC

XMF4MC

XMF5MC

XMF6MC

Applicable evaporation temperature (°C)

+ 10~-15°C

Refrigerants

R404A

power supply 

220V/380V50HZ

380V50HZ

 

Condenser

 

 

Number of fans (only)

1

1

1

2

2

Phoenix quantity (m³/h)

1×3200

1×3200

1×3200

2×3200

2×3200

Fan power (W)

1×60

1×60

1×60

2×60

2×60

 

 

Compressor huge cooling capacity

 

 

Evaporating temperature +5℃

Cooling capacity (W)

5270

7910

10450

12250

13,400

Electric power (W)

1920

3020

4100

5440

6130

 Evaporating temperature -5℃

Cooling capacity (W) 3750 5100 7000 8850 10100

Electric power (W)

1990

3100

3900

4700

5800

 Evaporation temperature -12℃

Cooling capacity (W) 2920 4100 5600 7200 8060

Electric power (W)

1910

2980

3700

4480

5370

interface

Outlet pipe interface

3/8"

3/8"

3/8"

1/2"

1/2"

Suction pipe connection

5/8"

5/8"

5/8"

3/4"

3/4"

Length (L) mm

970

970

970

970

970

Dimensions

Width (B) mm

410

410

410

410

410

Height (H) mm

835

835

835

1330

1330

Installation size

Length (D) mm

625

625

625

625

625

Width (E) mm

380

380

380

380

380

 Standard configuration of the unit: compressor, condenser, accumulator, pressure control, pressure gauge, filter

Devices, solenoid valves, terminals, etc.

 

Note: The
cooling capacity in the table is the ambient temperature of 32℃, and the
configuration can be added according to requirements

 

 

 

 

 

Message